APM402 Controls

  • Genset Product Range up to 1000 kW
  • Communications Modbus(R) RTU Standard, Modbus(R) TCP Standard, SNMP Optional
  • Paralleling No
  • NFPA 110 NFPA 110 Level 1

Standard Features

  • Provides metering, control and diagnostics for the generator set
  • Digital display and rotary pushbutton dial for easy access to data
  • Event history stores up to 1000 system events
  • Integrated voltage regulator to maintain consistent voltage output
  • Built-in alternator overload protection for safe generator operation
  • Alarm horn and light indication for shutdown and warning faults

Communication Features

  • Communication with RS-485 and Ethernet (RJ-45)
  • Supports Modbus RTU, Modbus TCP and SNMP version 1 protocols
  • Ethernet network requires an external Modbus/Ethernet converter
  • NFPA 110, Level 1 monitoring capable

Programmable Functions

  • One analog and two digital inputs standard
  • Optional two inputs available
  • One relay output standard
  • Optional five relay outputs available
  • Programmable for events, warnings and shutdowns